FINNED ELEMENT SINGLE / DOUBLE / QUADRUPLE |
OUTPUT WATT / M |
TUBE DIA mm |
TRENCH WIDTH mm |
TRENCH HEIGHT mm |
|
35 mm x 75 mm | SINGLE | 204 | 22 | 140 | 80 |
35 mm x 75 mm | DOUBLE | 387 | 22 | 250 | 80 |
75 mm x 75 mm | SINGLE | 520 | 22 | 150 | 150 |
75 mm x 75 mm | DOUBLE | 970 | 22 | 250 | 150 |
75 mm x 75 mm | QUADRUPLE | 1605 | 22 | 250 | 225 |
108 mm x 108 mm | SINGLE | 655 | 22 | 225 | 200 |
108 mm x 108 mm | DOUBLE | 1294 | 22 | 350 | 200 |
108 mm x 108 mm | QUADRUPLE | 2193 | 22 | 350 | 300 |
Outputs in watts per metre of finned element are based on LTHW 80 °C M.W.T, 20 °C E.A.T and 1 metre/second water velocity. The above WIDTH and HEIGHT dimensions are a guide and can be altered to suit individual requirements. For higher heat outputs, multiple finned elements can be used in a deeper trench heater body, Please contact TRENCH HEATING LTD for advice.
THE CORRECTION FACTORS FROM THE TABLE BELOW MUST BE USED TO ESTABLISH THE ACTUAL OUTPUT IN WATTS/M.
WATER VELOCITY |
CORRECTION |
MWT-EAT °C |
CORRECTION |
0.08 | 0.90 | 35 | 0.47 |
0.10 | 0.91 | 40 | 0.57 |
0.15 | 0.92 | 45 | 0.67 |
0.25 | 0.93 | 50 | 0.77 |
0.28 | 0.94 | 55 | 0.88 |
0.30 | 0.95 | 56 | 0.90 |
0.35 | 0.96 | 57 | 0.93 |
0.50 | 0.97 | 58 | 0.95 |
0.75 | 0.99 | 59 | 0.98 |
1.00 | 1.00 | 60 | 1.00 |
1.35 | 1.02 | 65 | 1.12 |
2.00 | 1.03 | 70 | 1.24 |